Dräger PSS 3000 SCBA Air Time Calculator

Select a model, choose your cylinder, enter pressure and breathing rate — duration is calculated instantly.

← All brands
🔥

Calculator

Ready
Reduce for partly-filled cylinder.
Dept. SOP safety buffer.
or enter custom RMV
Custom value takes priority when entered.
Select a model to get started.
Estimated Air Time
Usable pressure
Usable air volume
RMV used
Estimated time

The Dräger PSS 3000 is the entry-level PSS model: lightest in the range at 3.8 kg, EN 137 Type 2 certified, without integrated HUD or PASS in the standard configuration. It relies entirely on mechanical gauge reading and manual PASS devices for air and safety monitoring.

PSS 3000 as an entry-level unit: where it fits

The PSS 3000 is the lightest PSS model (3.8 kg without cylinder) and the lowest cost point in the Dräger structural firefighting range. It is used in departments with budget constraints, training academies that need a high volume of units, and auxiliary or wildland response teams where NFPA/EN electronics requirements are less prescriptive. Its EN 137 Type 2 certification is full structural firefighting capability — the entry-level designation refers to electronics scope, not breathing air performance.

Operating without integrated PASS: standalone device requirements

The PSS 3000 does not include an integrated PASS device. Departments using PSS 3000 units must supply standalone PASS devices in compliance with their applicable standard (EN 137 Type 2 requires PASS integration or attachment). Standalone PASS devices need separate donning, pre-entry function check, and monitoring. If crews have shifted from HUD/PASS-equipped units to PSS 3000, procedural adjustments are required to maintain equivalent safety monitoring.

PSS 3000 air time: same physics as PSS 7000 with identical cylinders

For the same 6.8L 300 bar carbon cylinder, the PSS 3000 provides identical air time to the PSS 7000 — because air time depends on cylinder volume and pressure, not the harness electronics. At 45 L/min (moderate work): 6.8 × 245 bar (300 − 55) = 1666 L ÷ 45 = 37.0 minutes. At 60 L/min: 27.8 minutes. The weight saving (0.7 kg lighter than PSS 7000) may marginally reduce RMV during extended entries, but this effect is minor compared to heat and stress variables.

FAQ

The standard PSS 3000 configuration includes neither integrated HUD nor integrated PASS. Standalone PASS devices must be used to meet EN 137 Type 2 safety requirements. This distinguishes the PSS 3000 from the PSS 4000 (PASS only) and PSS 5000/7000 (PASS + HUD).

No, not for the same cylinder. Air time depends on cylinder water volume, service pressure, reserve pressure, and RMV — not on which model carries the cylinder. Both PSS 3000 and PSS 7000 give identical calculated air time with a 6.8L 300 bar cylinder.

The PSS 3000 is typically chosen for cost, weight, or when standalone PASS devices are already standard issue. The PSS 4000 adds integrated PASS for convenience and reliability. If the standalone PASS administrative and donning burden is a concern, the PSS 4000 is the preferred step up.

Dräger SCBA Air Time Calculator – PSS 7000, PSS 5000, PSS 4000, PSS 3000

Dräger's PSS series (Pressluftatmer, meaning compressed-air breathing apparatus) covers four current generations designed for different operational requirements and budget profiles. The PSS 7000 is the flagship with full electronics; the PSS 3000 is the entry configuration without HUD or integrated PASS. All share the same air calculation logic — cylinder water volume multiplied by usable pressure — but differ in weight, electronics, and NFPA availability. Select the exact PSS model to match the cylinder and pressure options available for your unit.

PSS 7000 vs PSS 5000 vs PSS 4000 vs PSS 3000: what changes

The PSS 7000 is Dräger's full-featured model: integrated HUD, integrated PASS, and dual certification capability (EN 137 Type 2 and NFPA 1981 in some configurations). The PSS 5000 adds HUD and PASS but at a lower price point. The PSS 4000 drops the HUD. The PSS 3000 has no HUD and no integrated PASS. Air capacity and cylinder options are similar across models — the differences are electronics, harness options, and certification scope. This affects operational capability, not basic air volume.

EN 137 vs NFPA 1981 on Dräger PSS units

Some Dräger PSS 7000 configurations can be ordered with dual certification (EN 137 Type 2 and NFPA 1981), but this requires specific cylinder types and electronics packages. The standard European PSS 7000 is EN 137 Type 2 only. If your department procured NFPA-certified PSS units, confirm the cylinder operating pressure and reserve with your Dräger datasheet — NFPA configurations may operate at different pressure ratings than the EN standard 300 bar.

Dräger cylinder options: 221 bar steel vs 300 bar carbon

Dräger PSS cylinders are available in both 221 bar steel and 300 bar carbon fibre configurations. The 221 bar steel cylinder is older technology and provides less air per kilogram of cylinder weight, but is still in service at many departments. The 300 bar carbon cylinder is lighter and holds more air at equivalent water volume. When calculating air time, selecting the correct service pressure matters — a 6.8L cylinder at 221 bar holds significantly less air than the same volume at 300 bar.

Dräger alarm signals and reserve: matching your SOP

Dräger PSS units equipped with electronics typically provide audio/visual warnings at defined pressure thresholds. The low-pressure alarm is set by the manufacturer to comply with EN 137 requirements, but your department's operational reserve policy may be different from the alarm trigger point. Always enter your department's required reserve pressure in this calculator, not the alarm trigger value — they are not always the same number.

Why two firefighters with identical PSS units get different times

Same PSS model, same cylinder, same starting pressure — but actual air time varies by individual. The primary driver is RMV (Respiratory Minute Volume), which depends on fitness level, heat adaptation, stress response, task intensity, and mask seal. A well-fitted, trained firefighter in moderate conditions may breathe at 35–40 L/min. The same person in high heat during victim rescue may exceed 70 L/min. Use this calculator with your department's measured RMV data where available.

FAQ

Both have integrated HUD and PASS, but the PSS 7000 is the full flagship with dual certification capability (EN + NFPA in some configurations) and a more complete electronics package. The PSS 5000 is a mid-tier option with similar electronics at a lower price point. Cylinder and air volume options are comparable across both.

The standard PSS 3000 configuration does not include an integrated PASS device or HUD, making it the entry-level option in the PSS range. It is EN 137 Type 2 certified for structural firefighting but lacks the electronic safety features of the PSS 4000 and above.

Because usable air = water volume (L) × usable pressure (bar). A 6.8L cylinder at 221 bar minus 50 bar reserve gives 6.8 × 171 = 1163 L of air. The same cylinder at 300 bar minus 55 bar reserve gives 6.8 × 245 = 1666 L — about 43% more air from the same physical cylinder.

Some Dräger PSS 7000 configurations are available with NFPA 1981 certification, but this requires specific cylinder types, pressure ratings, and electronics. Not all PSS 7000 units sold in EN markets are NFPA compatible. Confirm with your Dräger datasheet and local procurement documentation.

For EN 137 Type 2 units operating at 300 bar, 55 bar is the common department reserve in European fire services. For units with electronic alarm systems, note that the alarm trigger and your department's required reserve may differ — always use your SOP reserve value in this calculator.

Notes & Safety

This is an estimate based on the values you enter. Real-world air consumption changes with workload, stress, temperature, mask seal, leaks, and individual physiology. Always follow your SOPs and monitor your pressure gauge continuously.